140404
4 Zone
Expandable Panel
Installer Manual
140404-100-03
Warning
Read all of the instructions before proceeding
Can cause electrical shock or equipment damage. Always turn off power to the heating/air
conditioning system prior to installing or adjusting the expandable zone panel. Wire the entire
panel before applying transformer power.
This panel is designed for professional installation, and is to be installed and configured as
described in this manual. Any other use is not recommended and will void the warranty.
Install disconnect and overload protection on circuits as required by code authorities having
jurisdiction for the installation.
Voltage Hazard
Caution
Expandable up to 32 Zones
Up to 4 Heat / 2 Cool
Conventional or Heat Pump
Store this manual for future reference.
Vue de la page 0
1 2 3 4 5 6 ... 21 22

Résumé du contenu

Page 1 - Installer Manual

®140404 4 Zone Expandable Panel Installer Manual140404-100-03 WarningRead all of the instructions before proceedingCan cause electrical shock or equ

Page 2 - Table of Contents

Configuration4Use the following instructions to configure the zone panel. The zone panel is factory set for a 1 Heat / 1 Cool Conventional System with C

Page 3 - Suitable Mounting Locations

Configuration4The configuration settings must be properly set in order for this zone panel to operate correctly. The Installer Settings will automatical

Page 4 - Figure 3

No. Installer Setting Display Factory Setting Comments (Notes follow table) Indicator Default Options (More information follows this

Page 5

System Checkout5After the wiring and configuration is complete, built in automatic zone panel tests may be used to verify equipment, damper, and panel

Page 6 - CONVENTIONAL THERMOSTATS

Fan Stage(s) Test ON or OFF This test turns on all fan stages and commands all dampers to open. Press SELECT to test or NEXT to advance to the next te

Page 7 - installer settings

LED COLOR INDICATION Thermostat LED’s (4 Positions) R Red 24 VAC available to Thermostat Y1 Yellow Thermostat First Stage Compressor Call Y2

Page 8 - ALWAYS PROVIDE

Number of Fan Calls currently being serviced. Check the panel LED if it is necessary to determine exactly which zones are calling for Fan Operation.16

Page 9 - Set Equipment Type to MSH

Error Conditions7The zone panel continually monitors various components of the zone system and will display a message when the following monitored con

Page 10 - Configuration

Outdoor Sensor Bad Displayed when an error has been detected with the outdoor sensor. This error must be corrected by servicing the zone panel outdo

Page 11

Adding More Zones8The zone panel can be expanded to up to 32 zones with 4 zones on the main panel and 28 total expansion zones. Additional zones must

Page 12 - NOTES - Configuration

Specifications 1 Storage temperature: -40˚–167˚F (-40˚–75˚C)Operating temperature: -22˚–167˚F (-30˚–75˚C)Voltage: 24 VAC, Nominal 60Hz 18-30 VAC Maxi

Page 13 - System Checkout

Example Wiring Options20Main PanelExpander PanelZones 5-6Expander PanelZones 7-8Expander PanelAs NeededDaisy Chain All Zones Located at Main PanelStar

Page 14 - (continued)

Example Wiring Options (continued)Daisy Chain Zones Located Remote to Main Panel (Up to 500 Feet)Main PanelExpander PanelZones 5-6Expander PanelAs Nee

Page 15 - LED COLOR INDICATION

Store this manual for future reference.Limited WarrantyWhen installed by a professional contractor, this product is backed by a 5 year limited warrant

Page 16

Suitable Mounting Locations 2 Mount the Zone Panel near the HVAC equipment. The panel can be mounted in any orientation on a wall, stud, roof truss, o

Page 17 - Plenum Sensor Bad

Wiring the Panel 3 Always turn off power to the heating/air conditioning system prior to installing or adjusting the Zone Panel. Wire the entire panel

Page 18 - Outdoor Sensor Bad

EM HEAT R Y1 Y2 W1/E/AX1 W2/AX2O/B/W3 G L CTHERMOSTAT ZONE 1 POCOMM P

Page 19 - Adding More Zones

Damper Wiring 3.1 Always turn off power to the heating/air conditioning system prior to installing or adjusting the zone panel. Wire the entire panel

Page 20 - Star Wiring All Zones

3 HEAT / 2 COOL R 24 VAC Power W1 Heat Call Stage 1 W2 Heat Call Stage 2 W3 Heat Call Stage 3 Y1 Cooling Call Stage 1 Y2 Cooling Call Stage 2

Page 21

Supply Air Sensor Wiring 3.3 Install the supply air sensor in the supply air plenum at least 2-3 feet after the heat exchanger and coil. Make sure the

Page 22 - Limited Warranty

Heat Pump Equipment Wiring 3.6NOTE: For Conventional Systems, see Section 3.5Connect a single or multi-stage heat pump system to the zone panel as sh