WARNING
Important Safety Information
1
Replacing Existing Thermostat
Builder Series
Non-Programmable Thermostats
Single Stage Heat / Cool
Conventional and Heat Pump
Multi-Stage 2 Heat / 1 Cool
Conventional and Heat Pump
Always turn off power to the air conditioning or heating system prior to
installing, removing, cleaning or servicing thermostat.
This thermostat is a dual power thermostat and either requires 24 Volts AC
Power or two (2) properly installed “AA” alkaline batteries for normal
operation and control of the heating or cooling system. Refer to “Low Battery
Detection and Replacement” section for more information.
This thermostat should only be used as described in this manual. Any other
use is not recommended and will void the warranty.
Specifications
Installation
Testing Your New Thermostat
Programming User Settings
Temperature Adjustment
Additional Operation
Features
Battery Replacement
Troubleshooting
Wiring Diagrams
1
2
3
4
5
6
7
8
9
1
Specifications
• Electrical Rating: 24 Volt AC (18-30 Volt AC)
1 amp maximum load per terminal
2 amp total maximum load (all terminals) (Model 1000, 1000NC)
3 amp total maximum load (all terminals) (Model 1200, 1200NC)
• Control Range: 45˚ - 90˚ F (7˚- 32˚ C)
Accuracy: +/- 1˚ F (+/- .5˚ C)
AC Power: 18-30 Volt AC
• DC Power: 3.0 Volt DC (2 AA Alkaline batteries included)
Model 1000, 1000NC: Compatibility with low voltage single stage gas, oil or
electric heating or cooling systems, including single stage heat pumps, can
also be used on 250mv to 750mv millivolt heating only systems.
Model 1200, 1200NC: Compatibility with low voltage multi-stage gas, oil or
electric heating or cooling systems, including multi-stage heat pumps.
Terminations, Model 1000, 1000NC: Rc, Rh, B, O, Y, W, G, C
Terminations, Model 1200, 1200NC: R, O, B, C, Y1, E/W1, G, W2
1
Specifications
cont.
Installation
2
1. Always turn off power to the air conditioning or heating system prior to
removing existing thermostat.
2. Remove the cover of your old thermostat and locate the wire terminals.
Do not remove wires from terminals yet.
3. Using small pieces of masking tape, label wires prior to removal from
terminals. Use the chart below to determine the new terminal designations
for your new thermostat.
MODEL
Before Installing, Programming or Operating,
PLEASE READ ALL INSTRUCTIONS
Old Terminal from
Existing Thermostat
New Terminal for
New Thermostat
(1000, 1000NC)
New Terminal for
New Thermostat
(1200, 1200NC)
Terminal
Description
V or Rc Rc Cooling
Transformer
M, 4, Rh, or R Rh Heating
Transformer
R, V-VR or VR-R R 24 VAC
B B B Reversing Valve
(Heating)
O O O Reversing Valve
(Cooling)
Y, Y1 or M Y Y1 Cooling or
Compressor for
HP System
E, H, W, or 4 W E/W1 1st Stage Heat
or Emergency Heat
G or F G G Fan Control
C, X or B C C 24 VAC Common
4. After labeling and removing all wires from terminals, unscrew the existing
thermostat sub-base from wall. Secure wires to prevent them from slipping
into the hole in the wall.
NOTE–MODEL 1000, 1000NC: This thermostat is designed for use with 24
Volt-AC low voltage single stage gas, oil or electric heating or cooling systems,
including single stage heat pumps and can also be used on 250mv to 750mv
millivolt heating only systems. Do not use this thermostat on applications with
voltages above 30 Volts AC.
NOTE–MODEL 1200, 1200NC: This thermostat is designed for use with 24
Volt-AC low voltage multi-stage gas, oil or electric heating or cooling systems,
including multi-stage heat pump systems. Do not use this thermostat on
applications with voltages above 30 Volts AC.
1000, 1000NC
MODEL
1200, 1200NC
Vue de la page 0
1 2 3 4 5 6 7

Résumé du contenu

Page 1 - Builder Series

WARNINGImportant Safety Information1Replacing Existing ThermostatBuilder SeriesNon-Programmable Thermostats Single Stage Heat / Cool Conventional an

Page 2 - Testing Your New Thermostat

23Installing Your New ThermostatWARNING!Read BEFORE TestingInstallation2cont.NOTE: If installing this thermostat in a new installation, locate the th

Page 3 - Temperature Adjustment

4Default Thermostat SettingsSetting Second Stage DifferentialSetting Temperature Differentials5Review Set Temperaturecont.Programming User Settings4Th

Page 4 - Battery Replacement

6Compressor Protection FeatureLow Battery Detection and ReplacementThis thermostat includes an automatic compressor protection feature to avoid potent

Page 5 - Wiring Diagrams

89cont.Symptom: OFF is shown in thermostat display and heating or cooling system will not start.Potential Solution: This indicates that the system is

Page 6

MODEL 1000, 1000NC: Single Stage Heat Pump SystemCompressorControlcont.Wiring Diagrams9Transformer Common(See NOTE 1)cont.Wiring Diagrams9R OReversin

Page 7 - WARRANTY

STORE THIS BOOKLET FOR FUTURE REFERENCE©2009 Braeburn Systems LLC • U.S. Patents D530,633; D527,658; 7,438,469 • All Rights Reserved. Made in