WARNING
Important Safety Information
1
Builder Series
Non-Programmable Thermostats
Single Stage Heat / Cool
Conventional and Heat Pump
Multi-Stage 2 Heat / 1 Cool
Conventional and Heat Pump
Always turn off power to the air conditioning or heating system prior to
installing, removing, cleaning or servicing thermostat.
This thermostat requires either 24 Volts AC Power or two (2) properly installed
“AA” alkaline batteries for normal operation and control of the heating or
cooling system. Refer to “Low Battery Detection and Replacement” section for
more information.
This thermostat should only be used as described in this manual. Any other
use is not recommended and will void the warranty.
Specifications
Installation
Testing Your New Thermostat
Programming User Settings
Temperature Adjustment
Additional Operation
Features
Battery Replacement
Troubleshooting
Wiring Diagrams
1
2
3
4
5
6
7
8
9
1
Specifications
• Electrical Rating: 24 Volt AC (18-30 Volt AC)
1 amp maximum load per terminal
2 amp total maximum load (all terminals) (Model 1000, 1000NC)
3 amp total maximum load (all terminals) (Model 1200, 1200NC)
• Control Range: 45˚ - 90˚ F (7˚- 32˚ C)
Accuracy: +/- 1˚ F (+/- .5˚ C)
AC Power: 18-30 Volt AC
• DC Power: 3.0 Volt DC (2 AA Alkaline batteries included)
Model 1200, 1200NC: Compatibility with low voltage multi-stage gas, oil or
electric heating or cooling systems, including multi-stage heat pumps.
Terminations, Model 1000, 1000NC: Rc, Rh, B, O, Y, W, G, C
Terminations, Model 1200, 1200NC: R, O, B, C, Y1, E/W1, G, W2
1
Specifications
cont.
Installation
2
MODEL
Before Installing, Programming or Operating,
PLEASE READ ALL INSTRUCTIONS
Model 1000, 1000NC: Compatibility with low voltage single stage gas, oil or
electric heating or cooling systems, including single stage heat pumps, can
also be used on 250mv to 750mv millivolt heating only systems.
Old Terminal from
Existing Thermostat
New Terminal for
New Thermostat
(1000, 1000NC)
New Terminal for
New Thermostat
(1200, 1200NC)
Terminal
Description
V or Rc Rc Cooling
Transformer
M, 4, Rh, or R Rh Heating
Transformer
R, V-VR or VR-R R 24 VAC
B B B Reversing Valve
(Heating)
O O O Reversing Valve
(Cooling)
Y, Y1 or M Y Y1 Cooling or
Compressor for
HP System
E, H, W, or 4 W E/W1 1st Stage Heat
or Emergency Heat
G or F G G Fan Control
C, X or B C C 24 VAC Common
1000, 1000NC
MODEL
1200, 1200NC
Replacing Existing Thermostat
Most thermostats have three parts:
The cover, which may snap or hinge over the existing thermostat.
The electronics or body, which controls the existing system.
The sub-base, where the wires attach through the wall to the existing system.
1. Always turn off power to the air conditioning or heating system prior to
removing existing thermostat.
2.
Carefully remove the cover and electronics body from the old thermostat sub-base.
Depending on the brand, these parts may pull off or need to be unscrewed. The
old sub-base should remain wired and on the wall until steps 4 and 5.
3. Label every old wire with the letter of the connection to which the wire is
attached. Example letters are R, M, Y etc. Depending on the brand of the old
thermostat, your letters may be different.
4. After labeling the old wires, loosen each connection and remove them from old
sub-base. Secure the wires to prevent them from slipping into the hole in the wall.
5. Remove the old sub-base from the wall, again being careful that the wires do
not slip into the hole in the wall.
6. Use the chart below to determine the new thermostat connections. As an
example, if the old thermostat had a G connection, it goes to G on the new
thermostat. Note the chart includes information for Braeburn
®
1000(NC) and
1200(NC) thermostats. Be sure to use the correct column for the new thermostat.
Vue de la page 0
1 2 3 4 5 6 7

Résumé du contenu

Page 1 - Builder Series

WARNINGImportant Safety Information1Builder SeriesNon-Programmable Thermostats Single Stage Heat / Cool Conventional and Heat Pump Multi-Stage 2 Hea

Page 2 - Testing Your New Thermostat

2 3Installing New ThermostatWARNING!Read BEFORE TestingInstallation2cont.NOTE: If installing this thermostat in a new installation, locate the thermo

Page 3 - Temperature Adjustment

4Default Thermostat SettingsSetting Second Stage DifferentialSetting Temperature Differentials5Review Set Temperaturecont.Programming User Settings4Th

Page 4 - Battery Replacement

6Compressor Protection FeatureLow Battery Detection and ReplacementThis thermostat includes an automatic compressor protection feature to avoid potent

Page 5 - Wiring Diagrams

8 9cont.Symptom: OFF is shown in thermostat display and heating or cooling system will not start.Potential Solution: This indicates that the system is

Page 6

MODEL 1000, 1000NC: Single Stage Heat Pump SystemCompressorControlcont.Wiring Diagrams9Transformer Common(See NOTE 1)cont.Wiring Diagrams9R OReversin

Page 7 - LIMITED WARRANTY

©2011 Braeburn Systems LLC • U.S. Patents D530,633; D527,658; 7,438,469 • All Rights Reserved. Made in China • 1000-100-011This warranty gives you spe